{"id":2570,"date":"2011-03-20T16:32:12","date_gmt":"2011-03-20T20:32:12","guid":{"rendered":"http:\/\/www.engineeringradio.us\/blog\/?p=3928"},"modified":"2023-04-30T14:30:08","modified_gmt":"2023-04-30T18:30:08","slug":"overhaul-of-the-onan-12jc4r-generator","status":"publish","type":"post","link":"https:\/\/www.engineeringradio.us\/blog\/2011\/03\/overhaul-of-the-onan-12jc4r-generator\/","title":{"rendered":"Overhaul of the Onan 12JC4R generator"},"content":{"rendered":"\n<p>I was fortunate enough to acquire this generator last fall. \u00a0It was new in 1969 and has unknown hours on it, but it appears in decent shape. \u00a0I am going to do a level two overhaul and install it as backup power for my house\/shop. \u00a0The first order of business is a complete inspection. \u00a0I discovered a few problems; the starter didn&#8217;t crank, the distributor was loose, and the carburetor had some burned-out chunk of metal attached to it.<\/p>\n\n\n\n<figure class=\"wp-block-image alignnone\"><a href=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"650\" height=\"389\" src=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator.jpg\" alt=\"Onan 12JC4R generator\" class=\"wp-image-2596\" srcset=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator.jpg 650w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-150x89.jpg 150w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-300x179.jpg 300w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-400x239.jpg 400w\" sizes=\"auto, (max-width: 650px) 100vw, 650px\" \/><\/a><figcaption class=\"wp-element-caption\">Onan 12JC4R generator<\/figcaption><\/figure>\n\n\n\n<p>First, the starter: \u00a0These units use a Prestolite MEO3006 starter, which is common to several Chrysler products from the late &#8217;60s and early &#8217;70s. \u00a0This is obviously a replacement unit, as it is not &#8220;Onan Green.&#8221; \u00a0When I hooked a battery up and tried to turn the motor over, the start relay clicked but nothing else happened. \u00a0I dismounted the starter and removed the starter solenoid. \u00a0The interior of the starter motor looked in good condition, which points to the solenoid. \u00a0Sure enough, I removed the back of that unit and found two wires burned through and a large blackened area. \u00a0While I had the starter off, I hooked it up to a 12-volt battery and it worked fine. \u00a0A new starter costs $469.00, and a new solenoid cost $59.00. \u00a0I opted for the solenoid.<\/p>\n\n\n\n<figure class=\"wp-block-image alignnone\"><a href=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-starter-solenoid.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"650\" height=\"431\" src=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-starter-solenoid.jpg\" alt=\"Onan 12JC4R burned out generator starter solenoid\" class=\"wp-image-2597\" srcset=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-starter-solenoid.jpg 650w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-starter-solenoid-150x99.jpg 150w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-starter-solenoid-300x198.jpg 300w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC4R-generator-starter-solenoid-400x265.jpg 400w\" sizes=\"auto, (max-width: 650px) 100vw, 650px\" \/><\/a><figcaption class=\"wp-element-caption\">Onan 12JC4R burned out generator starter solenoid<\/figcaption><\/figure>\n\n\n\n<p>The next thing is the distributor. &nbsp;I was checking the points and contemplating replacing the breaker points with an electronic ignition when I discovered the distributor could turn 1\/8 of a turn in each direction, as when making timing adjustments.<\/p>\n\n\n\n<figure class=\"wp-block-image alignnone\"><a href=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC-4R-generator-distributor.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"650\" height=\"445\" src=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC-4R-generator-distributor.jpg\" alt=\"Onan 12JC 4R distributor clamp\" class=\"wp-image-2600\" srcset=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC-4R-generator-distributor.jpg 650w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC-4R-generator-distributor-150x102.jpg 150w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC-4R-generator-distributor-300x205.jpg 300w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Onan-12JC-4R-generator-distributor-400x273.jpg 400w\" sizes=\"auto, (max-width: 650px) 100vw, 650px\" \/><\/a><figcaption class=\"wp-element-caption\">Onan 12JC 4R distributor clamp<\/figcaption><\/figure>\n\n\n\n<p>I used a 3\/8 box wrench and tighten up the clamp holding the distributor shaft. &nbsp;It took several turns and makes me wonder why it was loose. &nbsp;I will have to check the timing with a light once I get it running. &nbsp;This also could be why the generator was not running when we took it out of service.<\/p>\n\n\n\n<figure class=\"wp-block-image alignnone\"><a href=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/onan-12JC-4R-rotor.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"650\" height=\"412\" src=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/onan-12JC-4R-rotor.jpg\" alt=\"Onan 12JC 4R rotor and breaker points\" class=\"wp-image-2601\" srcset=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/onan-12JC-4R-rotor.jpg 650w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/onan-12JC-4R-rotor-150x95.jpg 150w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/onan-12JC-4R-rotor-300x190.jpg 300w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/onan-12JC-4R-rotor-400x253.jpg 400w\" sizes=\"auto, (max-width: 650px) 100vw, 650px\" \/><\/a><figcaption class=\"wp-element-caption\">Onan 12JC 4R rotor and breaker points<\/figcaption><\/figure>\n\n\n\n<p>As for the points, they look brand new, as do the rotor and distributor cap.<\/p>\n\n\n\n<figure class=\"wp-block-image alignnone\"><a href=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Chamion-H8C-spark-plug.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"650\" height=\"399\" src=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Chamion-H8C-spark-plug.jpg\" alt=\"Onan 12JC 4R generator spark plug, champion H8C\" class=\"wp-image-2599\" srcset=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Chamion-H8C-spark-plug.jpg 650w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Chamion-H8C-spark-plug-150x92.jpg 150w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Chamion-H8C-spark-plug-300x184.jpg 300w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/Chamion-H8C-spark-plug-400x245.jpg 400w\" sizes=\"auto, (max-width: 650px) 100vw, 650px\" \/><\/a><figcaption class=\"wp-element-caption\">Onan 12JC 4R generator spark plug, champion H8C<\/figcaption><\/figure>\n\n\n\n<p>The spark plugs look well used and the plug wires look original.<\/p>\n\n\n\n<p>Finally, there was an electric choke mechanism on the carburetor which is completely unnecessary for a propane-fueled unit. \u00a0The choke plate itself was wired open. \u00a0The electric choke was burned open, so I removed the assembly. \u00a0I then spent some time at the local NAPA cross-referencing parts. \u00a0Here is a tune-up list:<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><tbody><tr><td>Nomenclature<\/td><td>Onan part (old)<\/td><td>Onan part (new)<\/td><td>Napa Part<\/td><td>Alternate<\/td><\/tr><tr><td>Oil Filter<\/td><td>122A185<\/td><td>122-0193<\/td><td>1084<\/td><td>Fram PH16<\/td><\/tr><tr><td>Points*<\/td><td>166P245<\/td><td>166-0245<\/td><td>CS709<\/td><td>&nbsp;<\/td><\/tr><tr><td>Rotor<\/td><td>166P234<\/td><td>166-0234<\/td><td>AL58\/AL52<\/td><td>&nbsp;<\/td><\/tr><tr><td>Distributor cap<\/td><td>166B307<\/td><td>166-0235<\/td><td>AL91<\/td><td>&nbsp;<\/td><\/tr><tr><td>Condenser*<\/td><td>166P310<\/td><td>166-0310<\/td><td>AL38<\/td><td>&nbsp;<\/td><\/tr><tr><td>Ignition Coil**<\/td><td>166B310<\/td><td>166-0859-02<\/td><td>701002<\/td><td>PRX 405011<\/td><\/tr><tr><td>Plug wire #1<\/td><td>167A1410<\/td><td>167-1602<\/td><td>701064<\/td><td>&nbsp;<\/td><\/tr><tr><td>Plug wire 2,3,4<\/td><td>167A1409<\/td><td>167-1602<\/td><td>701063<\/td><td>&nbsp;<\/td><\/tr><tr><td>Spark Plug<\/td><td>167-4<\/td><td>167-<\/td><td>&nbsp;<\/td><td>Champ H8C***<\/td><\/tr><tr><td>Air Filter<\/td><td>140B640<\/td><td>140-1907<\/td><td>7-02241<\/td><td>&nbsp;<\/td><\/tr><tr><td>Starter<\/td><td>191C324<\/td><td>191-0324<\/td><td>&nbsp;<\/td><td>Prestolite MEO3006<\/td><\/tr><tr><td>Solenoid<\/td><td>N\/A<\/td><td>191-0433A<\/td><td>ST103<\/td><td>&nbsp;<\/td><\/tr><tr><td>*Electronic ignition set<\/td><td>N\/A<\/td><td>166-0825<\/td><td>&nbsp;<\/td><td>Pertronics 1545**<\/td><\/tr><tr><td>**Ignition coil W\/PRX 1545<\/td><td>&nbsp;<\/td><td>&nbsp;<\/td><td>&nbsp;<\/td><td>PRX 405011<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p>*Condenser and breaker points can be substituted for an electronic ignition kit, either Onan 166-0825 or Pertronics 1545 with Pertronics PRX 405011 coil.<br>**Pertronics electronic ignition must be used with Pertronics coil<br>***Champion RH8C plugs should be used with replacement wires without noise suppression plug boots.<\/p>\n\n\n\n<p>This is for an Onan 12JC generator circa 1969 with a Studebaker engine. Other models\/years may vary. \u00a0The other issue with this unit is there is no supervisory monitoring and control. \u00a0There is no oil pressure loss, overheating, or over-crank faults. \u00a0This is why the starter solenoid failed. \u00a0To remedy that situation, I started to design a better control circuit. \u00a0Then I looked around on the inner tubes and found somebody had already done this. \u00a0DynaGen makes the GSC400p which can monitor oil pressure, engine temperature, frequency, engine RPM, hours, voltage, and current. \u00a0It can fault for any out-of-tolerance condition, as programmed by the user.<\/p>\n\n\n\n<figure class=\"wp-block-image alignnone\"><a href=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/GSC400plus.jpg\"><img loading=\"lazy\" decoding=\"async\" width=\"600\" height=\"456\" src=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/GSC400plus.jpg\" alt=\"Retrofit generator controller\" class=\"wp-image-2602\" srcset=\"https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/GSC400plus.jpg 600w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/GSC400plus-150x114.jpg 150w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/GSC400plus-300x228.jpg 300w, https:\/\/www.engineeringradio.us\/blog\/wp-content\/uploads\/2011\/03\/GSC400plus-400x304.jpg 400w\" sizes=\"auto, (max-width: 600px) 100vw, 600px\" \/><\/a><figcaption class=\"wp-element-caption\">Retrofit generator controller<\/figcaption><\/figure>\n\n\n\n<p>I plan to install this in the original control box, leaving the original control circuit intact by using the remote start\/stop connections. &nbsp;I keep the original remote\/start\/stop switch and hand crank switch in place for use if the fancy controller fails.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>I was fortunate enough to acquire this generator last fall. \u00a0It was new in 1969 and has unknown hours on it, but it appears in decent shape. \u00a0I am going to do a level two overhaul and install it as backup power for my house\/shop. \u00a0The first order of business is a complete inspection. \u00a0I &hellip; <a href=\"https:\/\/www.engineeringradio.us\/blog\/2011\/03\/overhaul-of-the-onan-12jc4r-generator\/\" class=\"more-link\">Continue reading <span class=\"screen-reader-text\">Overhaul of the Onan 12JC4R generator<\/span><\/a><\/p>\n","protected":false},"author":4,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[3,17],"tags":[152,64],"class_list":["post-2570","post","type-post","status-publish","format-standard","hentry","category-general","category-maintenance","tag-emergency-power","tag-generator"],"_links":{"self":[{"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/posts\/2570","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/comments?post=2570"}],"version-history":[{"count":9,"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/posts\/2570\/revisions"}],"predecessor-version":[{"id":11848,"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/posts\/2570\/revisions\/11848"}],"wp:attachment":[{"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/media?parent=2570"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/categories?post=2570"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.engineeringradio.us\/blog\/wp-json\/wp\/v2\/tags?post=2570"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}