January 2017
M T W T F S S
« Nov    
 1
2345678
9101112131415
16171819202122
23242526272829
3031  

Archives

Categories

Computer guys…

Some guy posted this picture on Reddit:

Small Office network

Small Office network

In the comments, he gets blasted for being too neat and using wire ties.  I know a lot of IT guys that are not very neat with their work and document nothing.  This is a big problem in the industry and does not, contrary to popular belief, promote job security.  I have walked into some very messy situations in wiring closets and rack rooms over the years.  My solution is always the same; run some temporary wires for critical machines/functions, then get out the big wire cutters and start chopping.

Conduit fill

It may be surprising to some, but number of wires allowed in any given conduit is not “as many as can be jammed in there.” The National Electrical Code, AKA NEC or NFPA 70 gives specific guidance on the numbers of current carrying conductors allowed in any specific size and type of conduit.

This is due to the fact that current carrying conductors generate heat.  Cables enclosed in a conduit need to dissipate that heat so that the insulation on the cable doesn’t melt, which would be a bad outcome.

Conduit fill tables are found in Chapter 9 of the NEC.  There are several tables that give the number of conductors for each size and type of conduit.  Then there is the general rule of thumb that more than two cables, the maximum conduit fill is 40%.  This comes in handy when several different size conductors are being run in the same conduit.

An example of this is when several circuits are going across the room to the same general location, in this case, a row of transmitters and racks.  Instead of running individual conduits for all those units, one or two conduits from the electrical panel are run to a square wireway, then the individual circuits are broken out and wired from wireway to the individual loads.  In this case, the following equipment is being connected:

  • Harris FM25K: 100 amp 3 phase high voltage power supply (#2 THHN), 30 amp 3 phase transmitter cabinet (#10 THHN)
  • Harris FM3.5K: 70 amp split phase (#6 THHN)
  • Harris MW1A: 30 amp split phase (#10 THHN)
  • Two equipment racks: 20 amp single phase (#12 THHN)
  • Coax switch: 15 amp single phase (#14 THHN)
  • Dummy Load: 15 amp single phase (#14 THHN)
  • Antenna switch/dissipation network for AM station: 15 amp split phase (#14 THHN)
  • Convenience outlets for back wall: 20 amp single phase (#12 THHN)

Excluding grounding conductors, which will be addressed below, the total current carrying conductor count is thus:

  • #2 THHN: 3 each
  • #6 THHN: 3 each
  • #10 THHN: 7 each
  • #12 THHN: 6 each
  • #14 THHN: 6 each

Ampacities based on NEC table 310.16, THHN insulation in dry locations, maximum temperature rating is 90° C (194° F) based on ambient temperature of 30° C (86° F)

Grounding conductors for each of those circuits, based on NEC Table 250.122 (all conductors are copper):

  • 100 amp circuit: #8
  • 70 amp circuit: #8
  • 30 amp circuit: #10
  • 20 amp circuit: #12
  • 15 amp circuit: #14

The final conductor count is:

  • #2 THHN: 3 each
  • #6 THHN: 3 each
  • #8 THHN: 2 each
  • #10 THHN: 9 each
  • #12 THHN: 9 each
  • #14 THHN: 9 each

The plan is to use two 1 and 1/2 inch EMT conduits between the electrical service panel and the 4 x 4 square wireway. According to  NEC Chapter 9, Table 4, the 40% cross sectional size of this conduit is 526 mm2.  It is easier to simply use metric measurements for this.  The cross sectional wire areas are found in Chapter 9, Table 5.  Chart of various conductor sizes and areas:

Conductor Area (mm2) Total conductor Total area (mm2)
#2 THHN 74.71 3 224.13
#6 THHN 32.71 3 98.13
#8 THHN 23.61 2 47.22
#10 THHN 13.61 9 122.49
#12 THHN 8.581 9 77.229
#14 THHN 6.258 9 56.322

Thus, in order to break this up into two 1 and 1/2 inch conduits, the #2, #6 and #8 (main transmitter HV power supply, backup transmitter and grounds) are run in one conduit, the remaining circuits in the other.  The idea is that the main transmitter and backup transmitter will not be running simultaneously for long periods of time.  Those cable areas total 369.48 mm2, well within the 40% limit of 526 mm2 for 1 and 1/2 inch EMT.   The rest of the circuit’s cable areas total 256.041 mm2.  That leaves room for additional circuits in the second conduit if future needs dictate.  The extra conduit area will make pulling the wires through easy.

From the square wireway to the HV power supply, 1 and 1/4 inch conduit will carry the three #2 and one #8 ground.  1 and 1/4 inch EMT has a cross sectional area of 387 mm2, the conductors contained within will be 271 mm2.  Less room here, but still well withing the 40% limit.

Pictures will be posted when the project is done.

Documentation and labeling wire and cable

There are a myriad of details involved in building a studio, not to mention an entire facility.  Getting everything down on paper before a single wire is pulled is one way to insure that a neat, logical, and orderly product ensues.  For wire run documentation, I like to use Excel spreadsheet templates that I came up with.

There are several different types of cable, from 25 pair ATT style, to 16 or 24 pair shielded audio cable, to miscellaneous control cable, all of it has different color codes.  I found the Belden Technical info website to be an excellent source for various color codes.

Doing neat work is best way to keep things in order.  Notice all the wires are labeled.  All the ground conductors have heatshrink, which is required on insulation displacement terminations like 66 blocks, 110 blocks and ICON terminations.

ADC ICON termination block

ADC ICON termination block

Once all the work is done, the wire run sheets are updated with changes and additions (there are always changes and additions) which will keep the documentation accurate.

I made up several templates with the wire color code, pair number and cable information on each wire.  This allows the wire man to quickly enter changes to the wire information on the sheet.  At the end of the wiring project, these forms can be saved in several places, printed out and placed in a book or however the engineering manager wants to keep the information.

ATT 25 pair wire sheet

ATT 25 pair wire sheet .pdf

The excel spread sheet for this is here.

For 16 pair Gepco cable on 66 blocks, click here.

For 16/24 pair Gepco cable on ADC ICON Termination blocks, click here.

I say Gepco cable, any audio cable that is color coded with standard resistor color codes will work with these sheets, or the sheets can be adapted for use with other cables.

66 blocks audio and control for nextgen installation

66 blocks audio and control for nextgen installation

This is a good installation. The company I work for has several wiremen that are artists and do excellent work. Notice there is adequate room and light to work on the wall.  A dark, cramped area will lead to hurried work, poor workmanship, and mistakes in wiring.

Automation computer on slide out rack with cable management system

Automation computer on slide out rack with cable management system

All the cables to the rack mount computers are neatly dressed, which allows easier service.

Quad Star Microphone Cable

Or Star Quad Microphone Cable, depending on who is making it.

Star Quad Microphone Cable diagram

Star Quad Microphone Cable diagram

This has been around for quite a while, but many studio/broadcast engineers don’t understand it or don’t use it for some reason. Microphones and mic pickups produce relatively low signals when compared to line level audio.  Most microphone preamps have a gain of +50 dB, which means any noise gets amplified and even small things can become major problems quickly.

Gepco MP1201 Quadstar Microphone Cable

Gepco MP1201 Quadstar Microphone Cable

Under general conditions, most balanced shield twisted pair (STP) audio cable such as the standard Belden 8450 is adequate for stationary microphone cable for short runs.  When cable is not permanently fixed in place, as in hand held microphones, microphones mounted on booms, or other non fixed microphone applications, then flexible cable must be used.  Star Quad cable has better noise specifications than standard flexible microphone cable.

The advantages of Star Quad cable for low impedance microphones (150 ohms) is that the parallel twisted pairs significantly reduces inductive reactance.  In AC circuits, inductive reactance acts as a low pass filter, gradually rolling off as the frequency is increased.  This effect is cumulative, the longer the cable run, the more inductive reactance is added to the circuit.  The result is microphone audio can have smeared or ill defined high frequency audio.

parallel inductance formula

parallel inductance formula

Using two parallel twisted pairs is similar to parallel resistors when it dealing with inductive reactance, it halves the value.

In addition to reducing inductive reactance, the tighter twist found in Star Quad cables reduces the CMRR by about 20 dB.  The Star Quad configuration keeps the conductors in the same relative position to each other as the cable is flexed and moved around.  All of this makes it superior to standard STP microphone cable.

Several companies manufacture Quad Star cables:

  • Belden: 1192A
  • Canare: L-4E6S
  • Gepco: MP1201
  • Mogami W2534
  • Cardas 4X24

The price of Star Quad cables runs about 40-60 cents per foot (more for the Belden, much more for Cardas) if purchased in bulk.  That is about the same range for two conductor mic cables.

As good as this cable is, I don’t think they had this in mind when they made it:

I wonder what the centripetal force on that cable is when the microphone is in full motion. Also, I’d bet that SM58 was none the worse for were after it’s crowd surfing moment.

TIA/EIA 568

Radio stations more and more revolve around networked computers.  Engineers need to understand computer networking, especially as it relates to audio distribution and playback.  Eventually, I see broadcast engineers being more computer science types rather than electrical engineering majors.

What I have found out about computer networking is this: it is not rocket science.  In fact, most of it is pretty easy.  Physical networking and cabling is similar to audio and TELOC cabling.  Automation computer servers themselves are not difficult to understand as most of them run on some type of windows program.  Other servers such as Apache for WWW and for FTP and streaming run on some type of LINUX OS.  LINUX is also not difficult to understand so long as one knows the right command line prompts.

The first part of understanding computers is networking.  Without a computer network, a computer is a glorified typewriter.  Almost every automation system and or digital editor requires some type of network.  Consoles and computers that use AOIP require well constructed networks in order to operate properly.  To that end; cabling choices, network interface devices such as switches and routers, patch panels and so forth need to be specified and installed with care.

Most often, it is the simple things that will trip an installer up.  The one area where I have found the most mistakes made is the pairs connection to various termination points.  There are two basic standards, TIA/EIA T568A and T568B.  Neither is better than the other, both are often identified on terminating devices such as jacks and patch panels.  The most important aspect to these standards for an installer is to pick one and stick with it.

TIA/EIA 568 color code

TIA/EIA 568 color code

When certifying networks, the most common problem I have encountered is crossed pairs.  Almost invariably, one end will be punched down with the A standard and the other with the B standard.  Jacks are particularly difficult, as the color coding stickers show both.  Many patch panels have a slide out, reversible card with is an either/or situation.  For some reason, I have stuck with the B standard and on any project I am managing, I get rid of all the A color codes I can find and tell the installers that B is the only acceptable termination standard.  That cuts down on a lot of errors and redos during certification.  That is good, it saves time and I hate redos.

Cat 5e wall jack set

Cat 5e wall jack set

You can see that this color code marking can lead to confusion.  I take a sharpie and cross out all the the A markings to avoid installation mistakes.

Incidentally, on any new network installation, Category 6 cable should be used.  As more and more data through put is required for network applications,  Category 6 Cabling has better performance specs and will likely have a longer service life than other cable.   It may be a little bit more expensive than Cat 5,  however, well worth the investment.  It would be a great mistake and waste of money to have to pull out the network and reinstall it in a few years because the cabling doesn’t have the required bandwidth.

Category 7 cabling is in the works.

Category 5e cable in AES/EBU applications

I love wire. I know, what a geeky thing to say, but it is true. For no reason that I can explain, I have always been fascinated with wire, cables, and electricity.

Category 5e and up cabling is amazing stuff.  Designed for computer applications, it can fulfill a wide variety of rolls in radio and television stations, mostly because of its high bandwidth capacity.  Category 5e cabling has a 100 MHz bandwidth, category 6 bandwidth is 250 MHz, with 6a (augmented) being 500 MHz. AES/EBU audio uses ATM and requires from 4-26 MHz bandwidth, depending on the sample rate (highest sample rate is 200 KHz).  Category 5e cable has a minimum common mode balance of -60 dB, which makes it nearly impervious to RF, electrical noise, mutual interference and other noise issues.

Further, each pair in a category 5e or 6 cable has a different twist rate, to reduce cross coupling between pairs.

Here is a chart of electrical characteristics for Cat 5e, Cat6, and Belden AES/EBU cable:

Category 5e Category 6 AES/EBU*
Impedance (ohms) 100 +/- 10% 100 +/- 10% 110 +/- 20%
Bandwidth (MHz) 100 250 52
DC resistance 1K Ft (ohms) 27.12 27.42 23.68
Capacitance per Ft (pF) 15 15 12
Velocity factor (%) 72 72 76
Common Mode Balance (dB) 60 63 30
NEXT -44.3 -53.4
Configuration UTP UTP SPT
Wire Solid Solid Stranded
Gauge 24 23 24

* Belden 1800F

Specifications above are for Belden cabling, but are typical for high quality category cabling available from other sources as well.

Although the AES/EBU cable specifications call for 110 ohm impedance cable, that specification is pretty loose, calling for +/- 20%, which means 88 to 132 ohm cable will work well.  Category 5e and 6 cable is 100 ohm impedance, +/- 10%, which translates to 90 to 110 ohms, nominal.

Category 5 and 6 cabling can also be used for analog audio, RS232 and RS485 applications.  One area of caution, however, is for T-1 or fractional T-1 services.  On the DS side (between the smart jack and the CSU), T-1 type service runs 3 volts peak to peak.  That is much higher than AES/EBU or ethernet, which run 1 volt peak to peak.  As a result, cables in this type application should be 22 gauge or higher to reduce emissions from the cable.

Shielded category cable is available in Cat5 and 5e.  The shielding acts to reduce emissions from the cable in low noise environments.  It can also act to reduce RF fields around the cable pairs, so long as the proper cable terminations for shielded cable (RJ-45 or more properly 8P2C connectors) are used and installed correctly.  The shield must be connected to a ground on at least one end.  I know a facility that has all shielded Cat5 cable, but they used standard RJ-45 connectors, so both ends of the shield are floating, which completely defeats the purpose of the shield.

Cat5e 25 pair cable25 pair category 5e cable is available for trunk cabling between studios and the technical operations center.  For one studio project, I purchased pre-made cables with RJ-21 connectors on both ends.  Those connectors were then plugged into KRONE LSA-PLUS blocks.  Cable, connectors and blocks were all 100 ohm impedance, category 5 equipment.  Since we did not have to strip any insulation or punch down any wires, we pulled and terminated the studio to rack room trunk cables for five air studios and three production rooms in one morning.  This greatly sped up the studio build out process.

The studios and TOC use SAS 32KD (Sierra Audio Systems) audio router and Rubicon SL consoles, so most of the audio is AES/EBU.  There are, however, several analog audio sources that are included in this system, things like telephone caller audio, off air monitors, satellite feeds and remote broadcast sources.

This facility is located about 1 mile away from a 5 KW AM station on 850 KHz.  Several concerned people commented on the possibility of RFI on the cabling.   In the five years since that project was completed, there have been zero issues with the cabling or the audio quality.

One thing to consider in these installations is the length of the cabling and the sample rate being used across the network.  The capacitance per foot is the deciding quality in cable lengths.  This is because capacitance, which is the ability to store an electrical charge, will begin to distort the signal (turn it into a saw tooth waveform) in the cable if certain lengths are exceeded.  A good way to calculate maximum cable runs is thus:

Most professional AES/EBU devices sample 24 bits per channel, if the sample rate is 48 KHz, the 24 bits x 48,000 Hz = 1,152,000 bits per second per channel.  For stereo, as most applications will be, that is doubled to 2,304,000 bits per second, or 2.3 Mbps.  There is some overhead in an AES/EBU signal, so, for arguments sake, we will call it 4 MHz.

In this facility, the sample rate is locked at 48 kHz by a master clock.  The longest cable length is 145 feet, which adds (15 pF x 145 Ft) up to 2,175 pF capacitance.  From the chart above, we know that Cat5e has a resistance of 27.42 ohms per 1000 feet, or 0.02742 ohms per foot.  That works out to be 145 feet x 0.02742 ohms = 3.9759 ohms.

To calculate the capacitive reactance, the following formula is used:

Xc= -1/(2π FC)

Where Xc is the capacitive reactance, F is the frequency in Hz and C is the capacitance in Farads.

Therefore Xc = -1 / (2 x 3.1415 x 4,000,000 x 0.000000002) = -19.89 ohms.

The characteristic impedance of Cat5e and Cat6 is 100 ohms.  The DC resistance is 3.97 ohms and the capacitive reactance is -19.89 ohms, make the circuit impedance of a properly terminated cable 145 foot cable 84.08 ohms.

The design formula for a low pass filter is thus:

fc = 1/(2πRC)

Where fc is the cutoff frequency, R is the resistance and C is the capacitance.

Therefore, fc= 1/(2 x 3.1415 x 3.9759 ohms x 0.000000002 farads) = 20,014,958 Hz or 20 MHz.

Generally speaking, one should try to keep the capacitance below 2500 pF in a 10 Mbps circuit.  Belden datatwist 1212 cable has a 4.0 dB insertion loss and a 23.0 dB return loss per 100 meters (328 feet) at 4 Mhz.

145 feet is well within the limits of this cable for AES/EBU applications.

Further, all cable circuits need to be properly terminated to reduce return loss.  Using common impedance wiring blocks, connectors and terminations help keep return loss to a minimum.  Stranded wire works better in applications where cabling may move.  There are Cat5e and Cat6 stranded cables available.

As data transfer rates approach that of RF, ethernet, digital audio, and RF are going to seem more and more similar.  1000 Base T (1GBT) and 10000 Base T (10 GBT) networks are coming.

Wire terminations

Radio studios involve quite a bit of wiring.  Runs between the console and equipment are pretty straight forward, whatever the connector required for the equipment to whatever the connector required for the console.   When it comes to trunk runs between the rack room and the studio, however, some type of terminating block is required.

 alt=

66 block or M block insulation displacement wire termination

This particular cabling installation is for low level signaling, contact closures and the like.  It uses a Belden cable with 37 un-twisted wires which do not follow the standard Western Electric color code.  The color code can be found here.  If it where audio or data, the wires would be terminated differently.  That color code can be found here.  For more information on color codes and pinouts, see this post.

Many engineers use the venerable 66 block or M block insulation displacement termination.  These terminal blocks were designed by ATT to terminate 25 pair 22 through 26 gauge solid wire.  The the original design was rated for category 3 (16 MHz or 10 mb/s) communications standards.  Newer designs are category 5 or 5e compliant (350 MHz or 100 mb/s).  Notice the part about solid wire.  Most audio wire is stranded and as such, the metal fingers on a 66 block will cause stranded wire to spread out loosing contact with the terminating finger.  This causes intermittent connections and audio dropouts, which I have experienced often (before I knew better, I used 66 blocks when building studios).  The way to cure audio dropouts on a 66 block is to heat the termination fingers with a soldering iron.  This melts the wire insulation and gets it out of the way.  In the long run, it is better to use more suitable terminations.

Krone LSA-PLUS 110 type wire termination block

Krone LSA-PLUS 110 type wire termination block

The 110 block is updated version of punch block for high speed networks.  it is also designed for 22 through 26 gauge solid wire.  This is the termination used on category 5, 5e, 6 patch panels and RJ-45 jacks.  They are also formed into block type terminations the size of small 66 blocks.  The 110 block is designed for 500 MHz (1 gb/s) or greater bandwidth.  Krone makes a version of a 110 block called LSA-PLUS which is an acronym that stands for: Lötfrei, Schraubfrei, Abisolierfrei, Preiswert, Leicht zu handhaben, Universell anwendbar, Sicher und schnell.  Which translates to: no solder, no use of screws, no insulation removal, cost effective, easy to use, universal application, secure and fast.  Unlike a standard 110 block, the Krone block is designed for solid or stranded wire.  110 blocks are acceptable for use with AES/EBU digital audio at sample rates greater than 268 KHz as well as gigabit networks and analog audio.

In very old installations, I have seen christmas trees.  This is a wire wrap system where wires are wrapped around metal fingers that form the shape of a pine tree, hence the name.  They were very popular in the fifties and sixties and only work with solid wire.  It is also time consuming work and requires special tools and skills.  Wire wrapping is a bit of a lost art.

Christmas Tree wire wrap termination block

Christmas Tree wire wrap termination block

Screw barrier strips have been used to terminate audio cables from time to time.  I wouldn’t consider this method because it is too time consuming, takes up too much space and is difficult to label.

ADC ICON wire termination block

ADC ICON wire termination block

ADC makes a good termination block called ICON (Integrated Cable Organization Network) which uses QCP (Quick Connect Panel) connectors.  the connectors are small square devices that are insulation displacement termination (like 66 and 110 blocks) but require a special tool to “punch down.”   This particular type connector is well suited for stranded wire from 22 through 26 AWG.  QCP connectors are also used on some of ADC’s patch panels and other audio products.  Like any other termination technology, they are only as good as the person punching down the wires.  QCP connections are small high density devices, I have seen them get mangled by a someone in a hurry who got his punch down tool across two of the terminals by accident. ICON blocks can be used for digital audio, however, they do not maintain the 110 ohms impedance of most digital type audio cables (neither do XLR connectors, by the way).  This can lead to some return loss, which on longer cable runs can cause problems.

Radio Systems Studio Hub wiring diagram

Radio Systems Studio Hub wiring diagram

Radio systems prefers RJ-45 connectors with Category 5 cable, something they call Studio Hub.  These are 110 blocks as noted above, but designed primarily for computer networks.  Radio Systems discovered that the impedance of most audio cable is very close to that of computer network cable, audio cable is designed for 110 ohm impedance vs. computer network cable which is designed for 100 ohm impedance.  Therefore, RJ-45 connectors and shielded or unshieled twisted pair work well with balanced professional audio, either analog or digital.

For analog audio wires, ICON blocks seem to be the best, most secure high density termination system.  In all my years of using them, I have never had a connection go bad.  110 block and other category 5 or 5e systems also work well.  For digital audio, Krone blocks or 110 blocks need to be used in order to maintain the full bandwidth characteristics of the cable being used.  Using in appropriate cable and or terminations in digital audio circuits often leads to impedance mismatches and high return losses in the system.

Axiom


A pessimist sees the glass as half empty. An optimist sees the glass as half full. The engineer sees the glass as twice the size it needs to be.

Congress shall make no law respecting an establishment of religion, or prohibiting the free exercise thereof; or abridging the freedom of speech, or of the press; or the right of the people peaceably to assemble, and to petition the Government for a redress of grievances.
~1st amendment to the United States Constitution

Any society that would give up a little liberty to gain a little security will deserve neither and lose both.
~Benjamin Franklin

The individual has always had to struggle to keep from being overwhelmed by the tribe. To be your own man is hard business. If you try it, you will be lonely often, and sometimes frightened. But no price is too high to pay for the privilege of owning yourself.
~Rudyard Kipling

Everyone has the right to freedom of opinion and expression; this right includes the freedom to hold opinions without interference and to seek, receive and impart information and ideas through any media and regardless of frontiers
~Universal Declaration Of Human Rights, Article 19

...radio was discovered, and not invented, and that these frequencies and principles were always in existence long before man was aware of them. Therefore, no one owns them. They are there as free as sunlight, which is a higher frequency form of the same energy.
~Alan Weiner

Free counters!