I Got The Air Conditioner Blues

Back in the day, when tube transmitters ruled the broadcast world, common practice was to have a big cooling fan moving outside air through the transmitter building connected to a thermostat.  Temperature swings of 30 to 40 degrees were common, however, the tube rigs could handle almost any temperature that didn’t melt plastic or freeze water.

Today’s solid state transmitters are not that rugged.  They like to have there rooms around 70 degrees +/- 10 degrees or so.  Not to mention the other computer controlled equipment commonly found at a transmitter site.  Things like air chain processors, STLs, remote controls, etc.  So, lots of air conditioning is the norm, and with lots of air conditioning comes lots of maintenance.

Air handler air filters need to be checked and replaced often.  Condenser coils seem to attract every type of flying debris on the planet and need to be cleaned once, possible twice per year depending on tree and weed species near the site.  Even with the preventative maintenance, occasionally things like this happen:

AC condenser frozen dryer and piping

AC condenser frozen dryer and piping

Of course, the entire cooling coil inside is frozen solid.

This condenser is low on refrigerant, causing icing problems.  It has a slow leak somewhere and is about to be replaced.  Other reasons for this happening are malfunctioning or non-existent low ambient kit on the condenser fan.  Sometimes less than knowledgeable persons will install a 5 ton unit designed to run throughout the year but not take into account the effect of moving below freezing air at high speed across the coils.  Insufficient air moving across the cooling coil will also cause this.  Insufficient air flow can be due to plugged air filters or clogged fan/blower blades.

This one is even better (same condenser unit):

AC condenser broken fan

AC condenser broken fan

The fan blade is sheared off and jammed into the condenser coil.  This happened during power transfer from generator power to commercial power.  Naturally, it was at 1 am in the morning after a pole mounted transformer had been replaced.  When the building transfered back to commercial power, I went outside to use the “bathroom” before my two hour drive back home.  I though I smelled something hot, you know that cooked paint/plastic smell, but couldn’t really track it down… the winds were kicking up and another thunderstorm was on the way.

The next afternoon, however, when the sun was up and the site was working on one air conditioner, the temperature alarm went off.  Upon arrival, I found the condenser breaker tripped, resetting it caused the building lights to dim.  The fan motor was shorted to case.  I would theorize the aluminum fan blade suffered from metal fatigue, likely because the blades were not balanced causing a vibration.  When the power transfer occurred, there was just the right combination of torque and centripetal force to cause the blade to rip, then lodge in the condenser coil.

The fan motor has replaced, but I think it is time to replace the whole condenser unit, which will be expensive.

AC&R Gauge set

AC&R Gauge set

I found having a set of gauges to check the head pressure and suction is a good diagnostic tool to quickly pinpoint problems with HVAC units.  This way, when the HVAC tech shows up, you can quickly point him in the right direction.

Be Sociable, Share!

3 comments to I Got The Air Conditioner Blues

  • J. Aegerter

    A good HVAC man could install pressure relays that would open the control circuit under high head pressure, and possibly also warn you with a Sensaphone or Broadcast “Fools” alarm unit, along with saving the equipment. All of our installations have “sight glasses”, low temperature lock-out relays and the aforementioned line set pressure relays. Yearly cleaning of condenser coils with a mild acid wash keeps the fins clear of seeds and dirt which keeps the compressor happy.

  • Sight glasses don’t always tell the story. You will frequently see bubbles on start up. Someone will misinterpret that to mean something is amiss when it in fact is not. The unit has to run for a period and stabilize and even with that I take sight glass readings with a a grain of salt. I would rather know thew suction & liquid line pressures are and the outdoor ambient.

  • Ed

    The sight glass is only to shw the Quality of and not the Quanity of refrigerant

Axiom


A pessimist sees the glass as half empty. An optimist sees the glass as half full. The engineer sees the glass as twice the size it needs to be.

Congress shall make no law respecting an establishment of religion, or prohibiting the free exercise thereof; or abridging the freedom of speech, or of the press; or the right of the people peaceably to assemble, and to petition the Government for a redress of grievances.
~1st amendment to the United States Constitution

Any society that would give up a little liberty to gain a little security will deserve neither and lose both.
~Benjamin Franklin

The individual has always had to struggle to keep from being overwhelmed by the tribe. To be your own man is hard business. If you try it, you will be lonely often, and sometimes frightened. But no price is too high to pay for the privilege of owning yourself.
~Rudyard Kipling

Everyone has the right to freedom of opinion and expression; this right includes the freedom to hold opinions without interference and to seek, receive and impart information and ideas through any media and regardless of frontiers
~Universal Declaration Of Human Rights, Article 19

...radio was discovered, and not invented, and that these frequencies and principles were always in existence long before man was aware of them. Therefore, no one owns them. They are there as free as sunlight, which is a higher frequency form of the same energy.
~Alan Weiner

Free counters!